Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 11:37 AM
  • B 0720_B 0719 _29112017_035207.mp4

Date
11/29/2017
W/O
674032
Weather
Dry
Operator/Surveyor
ERUIZ
Sewer ID
Z00110
PipeID
P09394
Time
3:37 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5147
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_674032_TV22155_DEC2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0720
Downstream MH
B 0719
Dir. of Survey
Downstream
Length Surveyed
418.3 ft.
Total Length
418.3 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
246
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
246
Pipe schematic from manhole B 0720 to B 0719
MH: B 0720MH: B 0719downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 07200 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area3.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start23 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"73 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start73 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish75.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"124.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"176.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"225.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"277.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"326.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"415.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish418.2 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK418.3 ft. AMH - Downstream Manhole, Survey Ends - B 0719

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
73SAP
75.4TFC
225.6TFC
326.2TFC
124.5TFC
73SAP
23TFC
277.3TFC
3.7SAP
0AMHB 0720
418.3AMHB 0719
415.4SAP
0MWM
176.5TFC
0MWL
418.2MGOLATERAL AT MH 3 OCLOCK

Properties (6)

additional_info
SC346457
custom_field_two
2
customer
LACSD
datetime
2017-11-29T03:37:27-08:00
documentation
PROPIPE
is_lateral_inspection
false