Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2017, 11:52 AM
  • 18 0660_18 0659 _21112017_035242.mpg

Date
11/21/2017
W/O
668744
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14509
Time
3:52 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5042
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
WO_668744_TV18081_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0660
Downstream MH
18 0659
Dir. of Survey
Downstream
Length Surveyed
343.9 ft.
Total Length
343.9 ft.
Structural Index
3
Structural Quick
413G
Structural Rating
132
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
132
Pipe schematic from manhole 18 0660 to 18 0659
MH: 18 0660MH: 18 0659downstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06600 ft. MWM - Water Mark, 25 %of cross sectional area20.8 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES25.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start46.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish46.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start50.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish50.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start55.4 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES68.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish225.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start268.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish273.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start310.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish310.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES343.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0659

Observation photos (8)

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    20.8 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    25.5 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    46.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    50.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    55.4 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    225.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    306.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    310.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
310.6CM
50.7CL
25.5CL
55.4FM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
306.5CL
46.3CL
50.7CM
343.9AMH18 0659
68.6TFC
273.8TFC
0MWL
268.9TF
20.8CS
73.3TFC
225.9CM
0AMH18 0660
0MWM
173.6TFC
270.1CM
225.9CM
310.5CL
168.8TFC
46.4CL

Properties (6)

additional_info
SC346271
custom_field_two
2
customer
LACSD
datetime
2017-11-21T03:52:19-08:00
documentation
PRO-PIPE
is_lateral_inspection
false