Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2016, 09:25 AM
  • 05 1892_05 1891 _05082016_022554.mp4

Date
08/05/2016
W/O
579954
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00491
PipeID
P07119
Time
2:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3627
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 2
City
ROLLING HILLS ESTATES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
40
Purpose
Routine Assessment
Project
WO_579954_TV05079_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1892
Downstream MH
05 1891
Dir. of Survey
Downstream
Length Surveyed
318.4 ft.
Total Length
318.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
3121
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 05 1892 to 05 1891
MH: 05 1892MH: 05 1891downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18927.8 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6" - ROOTS9.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"14.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.9 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES68 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS91.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.5 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES218.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"311.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR313.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR318.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1891

Observation photos (5)

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: NO, 6" - ROOTS

    7.8 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6" - ROOTS

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    59.9 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    68 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    168.5 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

    311.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

Observations (16)

DistanceCodeObservation
7.8TBDROOTS
318.4AMH05 1891
9.2TBA
168.5CM
0MWL
59.9CS
223.4TFA
0MWM
313.3RFJ
91.6TFC
0AMH05 1892
94.4TBA
68TFDROOTS
311.1RFJ
218.3TFA
14.4TFC

Properties (6)

additional_info
SC306061
custom_field_two
4
customer
LACSD
datetime
2016-08-05T02:25:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false