Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2016, 10:44 AM
  • 04 0074_04 0038_24022016_024528.mp4

Date
02/24/2016
W/O
552531
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11811
Time
2:44 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3265
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
WO_552531_TV04009_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
15 in.
Upstream MH
04 0074
Downstream MH
04 0038
Dir. of Survey
Downstream
Length Surveyed
249 ft.
Total Length
249 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
2
O&M Quick
312J
O&M Rating
111
Overall Index
2
Overall Quick
Overall Rating
249
Pipe schematic from manhole 04 0074 to 04 0038
MH: 04 0074MH: 04 0038downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 04 00742 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start18.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.3 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURES27.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS74.1 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS76.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS125.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"128.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"136 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.3 ft. RML - Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES177.3 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS226.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish247.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK249 ft. AMH - Downstream Manhole, Survey Ends - 04 0038249 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (10)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURES

    25.3 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - FRACTURES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    27.8 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    74.1 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    76.6 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES

    177.3 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    177.3 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • General Observation - COCKROACHES IN MANHOLE

    249 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
27.8TFDROOTS
247.3DAGS
2DAGS
18.6CM
249MGOACTIVE CONNECTION AT MH 9 O'CLOCK
128.1TFA
249AMH04 0038
0MWM
228.8TFA
25.3TFDFRACTURES
0MWL
247.3CM
177.3RML
177.3TFDROOTS
136TFC
0MGOCOCKROACHES IN MANHOLE
0AMH04 0074
226.5TFA
76.6TFDROOTS
249MGOCOCKROACHES IN MANHOLE
74.1TFDROOTS
125.8TFA

Properties (6)

additional_info
SC225488
custom_field_two
4
customer
LACSD
datetime
2016-02-24T02:44:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false