Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 24, 2015, 03:39 PM
  • 15 0656_15 0655_20151123_015907.mp4

Date
10/24/2015
W/O
531432
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00606
PipeID
P12928
Time
8:39 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2287
Sewer Name
15 GRAND AVENUE TRUNK
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_531423_TV15027_OCT2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0656
Downstream MH
15 0655
Dir. of Survey
Downstream
Length Surveyed
89.3 ft.
Total Length
89.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0656 to 15 0655
MH: 15 0656MH: 15 0655downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01504.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.9 ft. MGO - General Observation - MAG COAT 30%29.4 ft. MGO - General Observation - UNMAPPED MANHOLE31.5 ft. MGO - General Observation - CONNECTION AT MH 3 0CLOCK ACTICE49.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"61.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"69.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"84.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish89.3 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK ACTIVE89.3 ft. AMH - Downstream Manhole, Survey Ends - 0159

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
61.5TF
0MWM
4.8SAV
0MWL
89.3MGOCONNECTION AT MH 9 OCLOCK ACTIVE
31.5MGOCONNECTION AT MH 3 0CLOCK ACTICE
29.4MGOUNMAPPED MANHOLE
84.7SAV
69.2TFC
0AMH0150
4.9MGOMAG COAT 30%
89.3AMH0159
49.7TFA

Properties (6)

additional_info
SC205369
custom_field_two
3
customer
LACSD
datetime
2015-10-24T08:39:32-07:00
documentation
PROPIPE
is_lateral_inspection
false