Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 23, 2015, 10:00 AM
  • 15 0655_15 0654_20151123_021401.mp4

Date
11/23/2015
W/O
531432
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00606
PipeID
P12927
Time
2:00 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2287
Sewer Name
15 GRAND AVENUE TRUNK
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_531423_TV15027_OCT2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0655
Downstream MH
15 0654
Dir. of Survey
Downstream
Length Surveyed
224.9 ft.
Total Length
224.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0655 to 15 0654
MH: 15 0655MH: 15 0654downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02000 ft. MWM - Water Mark, 25 %of cross sectional area3.8 ft. MGO - General Observation - MAG COAT 30%3.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"17.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"26.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"39.9 ft. MGO - General Observation - MAG PEELING FROM SURFACE60.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"66.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"91.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"115.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"145.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"188 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"215.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"219.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"221 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish224.9 ft. AMH - Downstream Manhole, Survey Ends - 0214

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 OCLOCK ACTIVE
0MWL
66.3TFC
60.7TFA
145.8TFA
219.1TFA
0AMH0200
3.8MGOMAG COAT 30%
17.5TBA
3.8SAV
91.5TFC
221SAV
26.8TFA
115.5TFA
39.9MGOMAG PEELING FROM SURFACE
14.6TFC
0MWM
215.4TFC
224.9AMH0214
188TFC

Properties (6)

additional_info
SC205369
custom_field_two
3
customer
LACSD
datetime
2015-11-23T02:00:49-08:00
documentation
PROPIPE
is_lateral_inspection
false