Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 24, 2015, 11:17 AM
  • 15 0642_15 0641_20151211_115803.mp4

Date
11/24/2015
W/O
531432
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00606
PipeID
P12914
Time
3:17 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2288
Sewer Name
15 GRAND AVENUE TRUNK
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
15
Purpose
Routine Assessment
Project
WO_531423_TV15027_OCT2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0642
Downstream MH
15 0641
Dir. of Survey
Downstream
Length Surveyed
317.7 ft.
Total Length
317.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0642 to 15 0641
MH: 15 0642MH: 15 0641downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 03194.4 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE 45%4.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start141.5 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"201.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"216.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"220.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"274.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"314.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish314.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish317.7 ft. AMH - Downstream Manhole, Survey Ends - 0328

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    39.7 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWM
314.3DAGS
4.4MGOMAG COAT THROUGHOUT PIPE 45%
4.4DAGS
201.8TBA
141.5TBA
0MWL
0MGOCONNECTION AT MH 9 OCLOCK
39.7SAV
314.3SAV
274.9TBA
220.5TFC
0AMH0319
317.7AMH0328
216.4TBA

Properties (6)

additional_info
SC205371
custom_field_two
3
customer
LACSD
datetime
2015-11-24T03:17:34-08:00
documentation
PROPIPE
is_lateral_inspection
false