Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 24, 2015, 03:35 PM
  • 15 0659_15 0658_20151123_024951.mp4

Date
10/24/2015
W/O
531432
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00606
PipeID
P12931
Time
8:35 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2287
Sewer Name
15 GRAND AVENUE TRUNK
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_531423_TV15027_OCT2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0658
Downstream MH
15 0659
Dir. of Survey
Upstream
Length Surveyed
307.6 ft.
Total Length
307.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0658 to 15 0659
MH: 15 0658MH: 15 0659upstream0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK ACTIVE0.1 ft. AMH - Upstream Manhole, Survey Ends - 02502.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish65.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"102.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"174.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"192.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"216.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"239.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"245.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"252.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"300.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"304.5 ft. MGO - General Observation - MAG COAT 20%304.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start307.6 ft. AMH - Downstream Manhole, Survey Begins - 0235307.6 ft. MWL - Water Level, 15 %of cross sectional area307.6 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0AMH0235
61.9TFA
307.6MGOCONNECTION AT MH 9 OCLOCK
133.1TFA
54.9TFA
7TFA
205.1TFC
307.6MGOCONNECTION AT MH 3 OCLOCK ACTIVE
91.3TFA
242.1TFA
3.1MGOMAG COAT 20%
307.5AMH0250
3SAV
304.9SAV
67.9TF
0MWL
0MWM
114.8TFA

Properties (6)

additional_info
SC205639
custom_field_two
3
customer
LACSD
datetime
2015-10-24T08:35:35-07:00
documentation
PROPIPE
is_lateral_inspection
false