Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2015, 10:22 AM
  • H 0370_H 0369_20151211_145816.mp4

Date
11/17/2015
W/O
531052
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00172
PipeID
P10708
Time
2:22 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2864
Sewer Name
H JOINT OUTFALL H - UNIT 2G
City
LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_531052_TV02281_OCT2015
Sewer Type
FACILITY TO FACILITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
H 0370
Downstream MH
H 0369
Dir. of Survey
Downstream
Length Surveyed
411.1 ft.
Total Length
411.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole H 0370 to H 0369
MH: H 0370MH: H 0369downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 0370 (0223)5.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start50.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES285.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"407.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish411.1 ft. AMH - Downstream Manhole, Survey Ends - HG 0369 (0235)

Observation photos (1)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    50.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
50.4FL
0MWL
411.1AMHHG 0369 (0235)
0MWM
285.2TBA
0AMHH 0370 (0223)
5.3DAGS
407.5DAGS

Properties (6)

additional_info
SC205629
custom_field_two
3
customer
LACSD
datetime
2015-11-17T02:22:34-08:00
documentation
PRO-PIPE
is_lateral_inspection
false