Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2015, 09:05 AM
  • 02 0865_02 0864_11122015_010555.mp4

Date
12/11/2015
W/O
525218
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00297
PipeID
P03432
Time
1:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2846
Sewer Name
02 OLD RIVER SCHOOL ROAD RELIEF TRUNK, SECTS 2&3
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_525218_TV02299_SEPT2015
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
02 0865
Downstream MH
02 0864
Dir. of Survey
Downstream
Length Surveyed
418.2 ft.
Total Length
418.2 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
237
O&M Index
2
O&M Quick
2Y00
O&M Rating
258
Overall Index
2
Overall Quick
Overall Rating
495
Pipe schematic from manhole 02 0865 to 02 0864
MH: 02 0865MH: 02 0864downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08650 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COATING 90%2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start141.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start370.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish417.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish418.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0864

Observations (9)

DistanceCodeObservation
2MGOMAG COATING 90%
0MWM
418.2AMH02 0864
417.5DAGS
0AMH02 0865
2DAGS
141.6DSZ
0MWL
370.9DSZ

Properties (6)

additional_info
SC204180
custom_field_two
5
customer
LACSD
datetime
2015-12-11T01:05:17-08:00
documentation
PRO PIPE
is_lateral_inspection
false