Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2015, 09:27 AM
  • E 0119_E 0118_08122015_012742.mp4

Date
12/08/2015
W/O
520989
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00032
PipeID
P11345
Time
1:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2841
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_520989_TV01102_SEPT2015
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
30 in.
Upstream MH
E 0119
Downstream MH
E 0118
Dir. of Survey
Downstream
Length Surveyed
440.3 ft.
Total Length
440.3 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
264
O&M Index
2
O&M Quick
2Q00
O&M Rating
176
Overall Index
3
Overall Quick
Overall Rating
440
Pipe schematic from manhole E 0119 to E 0118
MH: E 0119MH: E 0118downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 01190 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 40%15 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start110.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"381.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"440.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish440.3 ft. AMH - Downstream Manhole, Survey Ends - E 0118440.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2DAGS
110.9TBA
260.3TBA
0MWM
0AMHE 0119
440.3SAV
440.3AMHE 0118
15SAV
2MGOMAG COATING 40%
0MWL
381.6TB
440.3DAGS

Properties (7)

additional_info
SC204176
custom_field_two
3
customer
LACSD
datetime
2015-12-08T01:27:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
19870402