Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2016, 07:08 AM
  • G 0191_G 0190_20072016_000922.mp4

Date
07/20/2016
W/O
582914
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01180
PipeID
P01094
Time
12:08 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3617
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_582914_TV01100_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
G 0191
Downstream MH
G 0190
Dir. of Survey
Downstream
Length Surveyed
365 ft.
Total Length
365 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412M
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
148
Pipe schematic from manhole G 0191 to G 0190
MH: G 0191MH: G 0190downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - G 01910 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start363.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish364.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK364.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK365 ft. AMH - Downstream Manhole, Survey Ends - G 0190365 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    365 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
364.8MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2DAGS
0MWM
364.8MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMHG 0191
363.5DAGS
0MWL
365AMHG 0190
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
365MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
SC305796
custom_field_two
4
customer
LACSD
datetime
2016-07-20T00:08:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP