Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 21, 2016, 09:05 AM
  • G 0193_G 0192_21072016_020628.mp4

Date
07/21/2016
W/O
582914
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01180
PipeID
P01096
Time
2:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3618
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_582914_TV01100_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
G 0193
Downstream MH
G 0192
Dir. of Survey
Downstream
Length Surveyed
156.6 ft.
Total Length
156.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2F00
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole G 0193 to G 0192
MH: G 0193MH: G 0192downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - G 01930 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start136.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start154.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish154.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish156.6 ft. AMH - Downstream Manhole, Survey Ends - G 0192

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
136.5DSZ
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2DAGS
154.3DAGS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMHG 0193
156.6AMHG 0192
0MWL
154.3DSZ
0MWM

Properties (7)

additional_info
SC305797
custom_field_two
4
customer
LACSD
datetime
2016-07-21T02:05:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP