Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2016, 05:04 AM
  • 21 1035_21 1034_20160422_024121.mp4

Date
04/22/2016
W/O
557418
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00784
PipeID
P16139
Time
10:04 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3189
Sewer Name
21 SAN ANTONIO TRUNK
City
CLAREMONT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
06
Purpose
Routine Assessment
Project
WO_557418_TV21023_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
21 1035
Downstream MH
21 1034
Dir. of Survey
Downstream
Length Surveyed
382.9 ft.
Total Length
382.9 ft.
Structural Index
4
Structural Quick
4432
Structural Rating
22
O&M Index
2
O&M Quick
3122
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole 21 1035 to 21 1034
MH: 21 1035MH: 21 1034downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 10352 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start10.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO24.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"45.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"85.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"93.4 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: NO, 4", 1"99.9 ft. FM - Fracture Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES100.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"135.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"142.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"150.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"173.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"199.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"222.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"228.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES249.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"258.3 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR272.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"273.9 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES294.1 ft. CM - Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES297.8 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES299.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"321.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"323.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES348.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"371.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"373.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES380.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish382.9 ft. AMH - Downstream Manhole, Survey Ends - 21 1034

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    10.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO

  • Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

    93.4 ft. - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

  • Fracture Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

    99.9 ft. - Fracture Multiple, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    228.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR

    258.3 ft. - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    273.9 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    294.1 ft. - Crack Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

    297.8 ft. - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    323.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    373.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (33)

DistanceCodeObservation
382.9AMH21 1034
348.9TFC
323.1RFJ
93.4TBI
294.1CM
173.1TFC
99.9FM
371.7TFC
135.7TFC
297.8RFJ
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
222.4TFC
100.6TFC
85.8TFC
45.2TFC
0MWL
0AMH21 1035
373.1FM
2DAGS
24.8TFC
249.5TFC
321.9TFC
380.5DAGS
142.7TBA
10.4FL
272.2TFC
150.5TFC
199.8TFC
258.3RMJ
228.2FM
273.9FM
299.2TFC

Properties (6)

additional_info
SC226237
custom_field_two
2
customer
LACSD
datetime
2016-04-22T22:04:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false