Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2017, 09:08 AM
  • 08 0538_08 0537_10302017_030942.mp4

Date
10/30/2017
W/O
0635424
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00600
Time
2:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0665
Sewer Name
08 VICTORIA STREET TRUNK
City
RANCHO DOMINGUEZ
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
10282017VMR_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0538
Downstream MH
08 0537
Dir. of Survey
Downstream
Length Surveyed
277.6 ft.
Total Length
277.6 ft.
Structural Index
2
Structural Quick
332E
Structural Rating
65
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
65
Pipe schematic from manhole 08 0538 to 08 0537
MH: 08 0538MH: 08 0537downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:00AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area9.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT13.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE29.9 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - H37.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H37.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H41.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL45.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL49.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL86.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL89.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H94 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL110.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H118.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H118.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL130.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H142.6 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - H155.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL163 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H167.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL178.9 ft. MGO - General Observation - 12" VCP203.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H207.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H211.4 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H219.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H227.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H231.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL231.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H244 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL256.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL260.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H268.9 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - H272.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL277.6 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM

Observation photos (1)

  • General Observation - 12" VCP

    178.9 ft. - General Observation - 12" VCP

Observations (36)

DistanceCodeObservation
256.4FCSL
231.9FCSL
118.1FCH
49.5FCSL
0AMH3:00AM
231.9FCH
203.3FLH
0MWL
268.9FCH
89.7FCH
260.4FLH
9.3FCSLIGHT
142.6FCH
277.6AMH3:35AM
29.9FCH
37.7FCH
94FCSL
86.2FCSL
167.1FCSL
45.6FCSL
110.7FCH
130.5FCH
244FCSL
227.7FLH
178.9MGO12" VCP
155.3FCSL
118.1FCSL
163FCH
207.4FCH
211.4FCH
272.7FCSL
0MWM
41.4FCSL
13.2FCHAIRLINE
219.8FCH
37.7FCH

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-10-30T02:08:03-07:00
documentation
MARTIN,REVELES, MANANES, OLIVER III
is_lateral_inspection
false