Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 28, 2017, 01:09 PM
  • 08 0541_08 0540_10282017_Manual.mp4

Date
10/28/2017
W/O
0635424
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00021
PipeID
P00603
Time
6:09 AM
Certificate
U115-0622630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0664
Sewer Name
08 VICTORIA STREET TRUNK
City
RANCHO DOMINGUEZ
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
10282017VMR_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0541
Downstream MH
08 0540
Dir. of Survey
Downstream
Length Surveyed
275.1 ft.
Total Length
275.1 ft.
Structural Index
1
Structural Quick
1B00
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
1
Overall Quick
Overall Rating
13
Pipe schematic from manhole 08 0541 to 08 0540
MH: 08 0541MH: 08 0540downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 06:45 AM39.1 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES47.1 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES67.6 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES75.7 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES100.1 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES104.1 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES112.3 ft. CC - Crack Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES128.7 ft. CC - Crack Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES136.8 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES165.2 ft. CC - Crack Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES169.3 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES181.4 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES185.5 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES275.1 ft. AMH - Downstream Manhole, Survey Ends - 7:10 AM

Observations (17)

DistanceCodeObservation
165.2CC
128.7CC
112.3CC
275.1AMH7:10 AM
185.5CC
136.8CC
75.7CC
104.1CC
169.3CC
39.1CC
47.1CC
0MWL
0MWM
100.1CC
67.6CC
0AMH06:45 AM
181.4CC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2017-10-28T06:09:57-07:00
documentation
REVELES, MANANES, OLIVER III
is_lateral_inspection
false