Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2017, 09:59 AM
Date
07/18/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
Reveles
Sewer ID
Z00251
PipeID
P04544
Time
2:59 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0594
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Capital Improvement Program Assesment
Project
20170714VMR_DOWNEY_BELLFOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0212
Downstream MH
02 0211
Dir. of Survey
Downstream
Length Surveyed
64.6 ft.
Total Length
64.6 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0212 to 02 0211
MH: 02 0212MH: 02 0211downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Downstream Manhole, Survey Begins - 04:47 am0 ft. MWL - Water Level, 20 %of cross sectional area17.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES38.7 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES63.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 8"63.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 8" - Open64.6 ft. AMH - Upstream Manhole, Survey Ends - 04:58 am

Observations (8)

DistanceCodeObservation
64.6AMH04:58 am
0MWM
0AMH04:47 am
0MWL
38.7CC
63.9TFA
63.9TFOpen
17.1CL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-07-18T02:59:43-07:00
documentation
REVELES, MANANES, OLIVER
is_lateral_inspection
false