Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2019, 12:41 PM
  • H 0904_H 0903_6282019_054507.mp4

Date
06/28/2019
W/O
0771771
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00934
PipeID
P20377
Time
5:41 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8011
Sewer Name
H JOINT OUTFALL H - UNIT 5A RELIEF
City
WHITTIER
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
20190628DF_JOINT_OUTFALL_H_UNIT_5A_RELIEF
Material
RCP-PTL
Shape
Circular
Height
84 in.
Upstream MH
H 0904
Downstream MH
H 0903
Dir. of Survey
Downstream
Length Surveyed
282.1 ft.
Total Length
282.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole H 0904 to H 0903
MH: H 0904MH: H 0903downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:43 AM0.1 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MWL - Water Level, 15 %of cross sectional area171 ft. MGP - General Photograph282.1 ft. AMH - Downstream Manhole, Survey Ends - 6:02 AM282.1 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (2)

  • Water Level, 15 %of cross sectional area

    0.1 ft. - Water Level, 15 %of cross sectional area

  • General Photograph

    171 ft. - General Photograph

Observations (6)

DistanceCodeObservation
0AMH5:43 AM
282.1AMH6:02 AM
0.1MWM
0.1MWL
282.1MGOGREASE THROUGHOUT THE REACH (5%)
171MGP

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2019-06-28T05:41:47-07:00
documentation
FRANKLIN, BRAR, IGNACIO, RUVALCABA
is_lateral_inspection
false
year_laid
19920301