Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2019, 10:13 AM
  • 02 1112_02 1111_6262019_031501.mp4

Date
06/26/2019
W/O
0776968
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00285
PipeID
P03683
Time
3:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1247
Sewer Name
02 MONTEBELLO-RANDOLPH TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
20190626MDM_M0NTEBELLO_RANDOLPH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1112
Downstream MH
02 1111
Dir. of Survey
Downstream
Length Surveyed
232.3 ft.
Total Length
232.3 ft.
Structural Index
2
Structural Quick
352B
Structural Rating
49
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
57
Pipe schematic from manhole 02 1112 to 02 1111
MH: 02 1112MH: 02 1111downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:15AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING6.4 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H6.4 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - HAIRLINE6.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING14.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT25.4 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start30.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL38.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H42.1 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL43 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped57.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL61.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL68.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO77.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL89.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H89.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL109.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H117.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL137.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H149.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL153.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL153.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H157.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H193.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped196.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL204.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H216.6 ft. MWM - Water Mark, 20 %of cross sectional area219.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT BLISTERING PEELING219.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish232.3 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING

    6.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    25.4 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO

    68.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO

Observations (33)

DistanceCodeObservation
117.2FCSL
153.3FCSL
193.7TFCCapped
68.5DAGS
25.4DAGS
204.1FCH
232.3AMH3:45AM
77.2FCSL
157.2FLH
89.4FCH
6.8SSSPEELING
216.6MWM
6.4FCH
61.1FCSL
89.4FCSL
43TFCCapped
109.2FLH
6.4FLHAIRLINE
14.5FCSLIGHT
0AMH3:15AM
57.3FLSL
2.8SSSBLISTERING PEELING
196.4FLSL
219.9SSSSLIGHT BLISTERING PEELING
149.3FCSL
153.3FCH
42.1FCSL
30.1FCSL
38.1FCH
219.9DAGS
0MWM
137.2FCH
0MWL

Properties (6)

custom_field_three
SLIGHT FRACTURES-SLIGHT SPALLING BLISTERING PEELIN
custom_field_two
3
customer
LACSD
datetime
2019-06-26T03:13:00-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false