Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2019, 09:28 AM
  • 02 1113_02 1112_6262019_025139.mp4

Date
06/26/2019
W/O
0776968
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00285
PipeID
P03684
Time
2:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1247
Sewer Name
02 MONTEBELLO-RANDOLPH TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
20190626MDM_M0NTEBELLO_RANDOLPH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1113
Downstream MH
02 1112
Dir. of Survey
Downstream
Length Surveyed
51.1 ft.
Total Length
51.1 ft.
Structural Index
2
Structural Quick
3125
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 02 1113 to 02 1112
MH: 02 1113MH: 02 1112downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING FLAKING10.2 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING FLAKING OUTER SUFACE19.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE23.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING OUTER SURFACE23.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SLIGHT27.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING47.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H51.1 ft. AMH - Downstream Manhole, Survey Ends - 3:00AM

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING  FLAKING

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING FLAKING

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING FLAKING OUTER SUFACE

    10.2 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - PEELING FLAKING OUTER SUFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING OUTER SURFACE

    23.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING OUTER SURFACE

Observations (11)

DistanceCodeObservation
23.3SSSPEELING OUTER SURFACE
27.3SSSPEELING
0MWM
10.2SSSPEELING FLAKING OUTER SUFACE
51.1AMH3:00AM
2SSSPEELING FLAKING
19.5FLHAIRLINE
0MWL
23.3FCSLIGHT
0AMH2:45AM
47.1FCH

Properties (6)

custom_field_three
SPALLING=PEELING ,FLAKING OUTER SURFACE
custom_field_two
2
customer
LACSD
datetime
2019-06-26T02:28:49-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false