Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2019, 11:56 AM
  • B 1130A_B 1130_6242019_051646.mp4

Date
06/24/2019
W/O
0771118
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01125
PipeID
P13171
Time
4:56 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1244
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
20190624MDM_JOINT_OUTFALL_B_UNIT_6H
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 1130A
Downstream MH
B 1130
Dir. of Survey
Downstream
Length Surveyed
117.2 ft.
Total Length
117.2 ft.
Structural Index
2
Structural Quick
3225
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole B 1130A to B 1130
MH: B 1130AMH: B 1130downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWM - Water Mark, 10 %of cross sectional area16 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE17 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open18.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H26.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H26.8 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H32.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped50.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H55.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open59.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open87.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped103.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped106 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open108 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H111.5 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - H117.2 ft. AMH - Downstream Manhole, Survey Ends - 5:20AM

Observations (19)

DistanceCodeObservation
16FLHAIRLINE
32.3TFCCapped
59.8TFOpen
0AMH5:05AM
117.2AMH5:20AM
26.8FCH
87.4TFCCapped
26.8FCH
55.7TBOpen
17TFOpen
103.1TFCCapped
50.3FCH
0MWL
18.9FLH
111.5FCH
0MGOConn. @ Mh, 9 O' Clock. Active
0MWM
108FCH
106TFOpen

Properties (6)

custom_field_three
HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2019-06-24T04:56:51-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false