Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2019, 11:02 AM
  • B 1131_B 1130A_6242019_041741.mp4

Date
06/24/2019
W/O
0771118
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01125
PipeID
P26606
Time
4:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1244
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
20190624MDM_JOINT_OUTFALL_B_UNIT_6H
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 1131
Downstream MH
B 1130A
Dir. of Survey
Downstream
Length Surveyed
263.6 ft.
Total Length
263.6 ft.
Structural Index
2
Structural Quick
372A
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
41
Pipe schematic from manhole B 1131 to B 1130A
MH: B 1131MH: B 1130Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 10 %of cross sectional area11.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE12.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active26.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H27.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped30.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open32.3 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H32.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIIGHT44.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H53.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H62.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open64 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H64.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H65.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open75 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H80.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open86.8 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open87.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO - SL90.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H99.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped109.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H110.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open112.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H122 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped128.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL133.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open136.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open155.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped167.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped169.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open180 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H201.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open204.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped205.6 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H226.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL228.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped231.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open250.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open257.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped263 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active263.6 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observations (43)

DistanceCodeObservation
75FLH
30.5TFOpen
112.9FLH
87.3FLSL
263.6AMH4:50AM
11.3FCHAIRLINE
231.1TFOpen
110.9TFOpen
136.4TFOpen
109.6FLH
0MWL
62.8TFOpen
44.8FCH
180FLH
128.1FCSL
53.2FLH
263MGOConn. @ Mh, 9 O' Clock. Active
64FCH
32.3FCH
86.8TBOpen
257.7TFCCapped
90.7FCH
12.8TFActive
0AMH4:20AM
65.5TFOpen
80.5TFOpen
169.8TFOpen
228.6TFCCapped
26.4FCH
204.8TFCCapped
167.6TFCapped
226.8FCSL
27.7TFCCapped
201.5TFOpen
250.5TFOpen
99.6TFCCapped
155.6TFCCapped
64.1FLH
32.3FCSLIIGHT
0MWM
122TFCCapped
133.2TFOpen
205.6FCH

Properties (6)

custom_field_three
SLIGHT HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2019-06-24T04:02:47-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false