Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 22, 2016, 05:43 AM
  • 02 0808_02 0807_20160722_000407.mp4

Date
07/21/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03374
Time
10:43 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3660
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0808
Downstream MH
02 0807
Dir. of Survey
Downstream
Length Surveyed
321.2 ft.
Total Length
321.2 ft.
Structural Index
3
Structural Quick
3726
Structural Rating
33
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
38
Pipe schematic from manhole 02 0808 to 02 0807
MH: 02 0808MH: 02 0807downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08080 ft. MWM - Water Mark, 20 %of cross sectional area5.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start8.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES23.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES45 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES45.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"71.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES79.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"90.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish90.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES95.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"126.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES141 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"144.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"160.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO192.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"195.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"203.2 ft. CS - Crack Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES222 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES244 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"246.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"266.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES275.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES295.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"298.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"315.3 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES318.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish321.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0807

Observation photos (9)

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    5.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    8.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    8.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    71.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES

    203.2 ft. - Crack Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    266.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    275.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Downstream Manhole, Survey Ends - 02 0807

    321.2 ft. - Downstream Manhole, Survey Ends - 02 0807

Observations (31)

DistanceCodeObservation
298.8TFC
244TFC
95.2TFC
246.9TFC
141TFC
0MWL
144.4TFC
160.9CM
266.5CL
79.9TF
295.7TFC
23.1CL
0AMH02 0808
8.7SSS
71.4CM
90.5SSS
321.2AMH02 0807
8.7CL
192.5TFC
90.5CL
195.4TFC
45CM
315.3CM
222CM
203.2CS
275.5CM
45.9TFC
318.4DAGS
126.8CM
5.8DAGS
0MWM

Properties (6)

additional_info
SC305539
custom_field_two
3
customer
LACSD
datetime
2016-07-21T22:43:20-07:00
documentation
PROPIPE
is_lateral_inspection
false