Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2016, 07:58 AM
  • 02 0729_02 0728_20160725_022057.mp4

Date
07/25/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03283
Time
12:58 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3661
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0729
Downstream MH
02 0728
Dir. of Survey
Downstream
Length Surveyed
378.4 ft.
Total Length
378.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 02 0729 to 02 0728
MH: 02 0729MH: 02 0728downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 07290 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES20.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES80.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"82.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"194 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"196.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"212.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"310.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"312.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"375.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish378.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE378.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0728

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    82.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    212.6 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"

Observations (16)

DistanceCodeObservation
82.5TFC
0AMH02 0729
196.6TFC
378.4MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
194TFC
310.1TFC
375.1DAGS
2DAGS
0MWM
0MWL
80.2TFA
378.4AMH02 0728
212.6TBA
11.3CL
312.6TFC
20.5CM

Properties (6)

additional_info
SC305540
custom_field_two
4
customer
LACSD
datetime
2016-07-25T00:58:51-07:00
documentation
PROPIPE
is_lateral_inspection
false