Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2016, 09:30 AM
  • 02 0793A_02 0793_20160720_034102.mp4

Date
07/20/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03358
Time
2:30 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3658
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0793A
Downstream MH
02 0793
Dir. of Survey
Downstream
Length Surveyed
175.2 ft.
Total Length
175.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0793A to 02 0793
MH: 02 0793AMH: 02 0793downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 0793A0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE0.1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start29.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"32.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"62.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"62.8 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES65.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"103.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES129 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"132.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"172.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish175.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0793175.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    62.6 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    65.8 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    129 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"

Observations (16)

DistanceCodeObservation
0.1MWM
62.8CM
32.3TFC
175.2AMH02 0793
0AMH02 0793A
132.2TFC
0MWL
175.2MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
2DAGS
29.8TFC
62.6TFA
129TFC
103.3CM
172.9DAGS
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
65.8TF

Properties (6)

additional_info
SC305537
custom_field_two
4
customer
LACSD
datetime
2016-07-20T02:30:29-07:00
documentation
PROPIPE
is_lateral_inspection
false