Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2016, 06:03 AM
  • 02 0799_02 0798_20160720_001435.mp4

Date
07/19/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03365
Time
11:03 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3658
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0799
Downstream MH
02 0798
Dir. of Survey
Downstream
Length Surveyed
156 ft.
Total Length
156 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 0799 to 02 0798
MH: 02 0799MH: 02 0798downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 02 07990 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES39.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"42.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"53 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES65.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start98 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"107.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"150.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"150.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish152.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish156 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE156 ft. AMH - Downstream Manhole, Survey Ends - 02 0798

Observation photos (8)

  • General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

    0 ft. - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    13 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    53 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    65.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    98 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

    150.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    152.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (17)

DistanceCodeObservation
39.3TFC
150.3TFC
0MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
0AMH02 0799
156MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
152.7DAGS
53CM
156AMH02 0798
13CM
150.3CM
65.5CM
0MWL
107.3TFA
42.4TFA
98TFC
0MWM
2DAGS

Properties (6)

additional_info
SC305537
custom_field_two
3
customer
LACSD
datetime
2016-07-19T23:03:00-07:00
documentation
PROPIPE
is_lateral_inspection
false