Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2018, 08:45 AM
  • B 1537_B 1536_5212018_025702.mp4

Date
05/21/2018
W/O
070705
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01200
PipeID
P26347
Time
1:45 AM
Certificate
0-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0863
Sewer Name
B JOINT OUTFALL B - UNIT 6J RELIEF
City
LA CANADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20180521MDM_JOINT_OUTFALL_B_UNIT_6J_RELIEF
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 1537
Downstream MH
B 1536
Dir. of Survey
Downstream
Length Surveyed
362.8 ft.
Total Length
362.8 ft.
Structural Index
2
Structural Quick
2A00
Structural Rating
22
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole B 1537 to B 1536
MH: B 1537MH: B 1536downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:50AM0 ft. MWM - Water Mark, 30 %of cross sectional area5.2 ft. MGO - General Observation - WHITE BUILD UP ON PIPE5.2 ft. MGO - General Observation - WHITIE BUILD UP ON PIPE49.1 ft. SSS - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - LIGHT PEELING61.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING & BLISTERING PIPE63.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PIPE65.3 ft. MGO - General Observation - BEFORE AND AFTER POPPING BLISTER98 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - DEEP PEELING PIPE99 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PIPE130.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PIPE171.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - DEEP BLISTERING178.7 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - DEEP BLISTERING181.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - DEEP BLISTERING248.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING PIPE362.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - DEEP BLISTERING PIPE362.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING & BLISTERING PIPE362.8 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observation photos (13)

  • General Observation - WHITE BUILD UP ON PIPE

    5.2 ft. - General Observation - WHITE BUILD UP ON PIPE

  • General Observation - WHITIE BUILD UP ON PIPE

    5.2 ft. - General Observation - WHITIE BUILD UP ON PIPE

  • Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - LIGHT PEELING

    49.1 ft. - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - LIGHT PEELING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING & BLISTERING PIPE

    61.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING & BLISTERING PIPE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PIPE

    63.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PIPE

  • General Observation - BEFORE AND AFTER POPPING BLISTER

    65.3 ft. - General Observation - BEFORE AND AFTER POPPING BLISTER

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - DEEP PEELING PIPE

    98 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - DEEP PEELING PIPE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PIPE

    99 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PIPE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PIPE

    130.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PIPE

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - DEEP BLISTERING

    171.5 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - DEEP BLISTERING

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - DEEP BLISTERING

    178.7 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - DEEP BLISTERING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - DEEP BLISTERING

    181.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - DEEP BLISTERING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING PIPE

    248.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING PIPE

Observations (19)

DistanceCodeObservation
248.4SSSPEELING PIPE
0MWL
5.2MGOWHITE BUILD UP ON PIPE
98SSSDEEP PEELING PIPE
362.8AMH3:45AM
63.2SSSBLISTERING PIPE
61.4SSSPEELING & BLISTERING PIPE
171.5SSSDEEP BLISTERING
49.1SSSLIGHT PEELING
178.7SSSDEEP BLISTERING
362.3SSSDEEP BLISTERING PIPE
0AMH2:50AM
130.2SSSBLISTERING PIPE
65.3MGOBEFORE AND AFTER POPPING BLISTER
181.7SSSDEEP BLISTERING
99SSSBLISTERING PIPE
362.3SSSPEELING & BLISTERING PIPE
5.2MGOWHITIE BUILD UP ON PIPE
0MWM

Properties (6)

custom_field_three
BLISTERING VCP
custom_field_two
2
customer
LACSD
datetime
2018-05-21T01:45:00-07:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false