- Date
- 08/09/2017
- W/O
- 0646404
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00175
- PipeID
- P10779
- Time
- 1:03 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6795
- Sewer Name
- H JOINT OUTFALL H - UNIT 4
- City
- PICO RIVERA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 19A
- Purpose
- Capital Improvement Program Assesment
- Project
- 20170807MDM_JOINT_OUTFALL_H_UNIT_4
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 57 in.
- Upstream MH
- H 0329
- Downstream MH
- H 0328
- Dir. of Survey
- Downstream
- Length Surveyed
- 566.9 ft.
- Total Length
- 566.9 ft.
- Structural Index
- 3
- Structural Quick
- 3200
- Structural Rating
- 6
- O&M Index
- 4
- O&M Quick
- 4300
- O&M Rating
- 12
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 18
Pipe schematic from manhole H 0329 to H 0328 Observation photos (6)

2 ft. - General Observation - MAG COAT 100% 9:00 TO 3:00 START

8 ft. - General Photograph - MAG COAT

175.9 ft. - Water Mark, 50 %of cross sectional area

245.3 ft. - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

401.2 ft. - General Observation - MAG COAT 100%

464.9 ft. - Surface Aggregate Visible, at 10 o'clock, within 8 inches of joint: NO - SEVERE AGG