Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2017, 09:06 AM
  • Section#6_F 0027_F 0026__852017__G6793.mp4

Date
08/05/2017
W/O
0646716
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10117
Time
2:06 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6793
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20170805MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0027
Downstream MH
F 0026
Dir. of Survey
Downstream
Length Surveyed
546.7 ft.
Total Length
546.7 ft.
Structural Index
4
Structural Quick
5D4U
Structural Rating
551
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
555
Pipe schematic from manhole F 0027 to F 0026
MH: F 0027MH: F 0026downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 6:55AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - 80% START 9:00 TO 3:0015.4 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT71.7 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUN REBAR UNDER MAG COATSPORATIC115.1 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR174.1 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish284.1 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR546 ft. MGO - General Observation - MAG COAT 80% FINISH546 ft. MGO - General Observation - MH CONN 3:00 ACTIVE546 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG546 ft. MGO - General Observation - MH CONN OPEN 9:00546.7 ft. AMH - Downstream Manhole, Survey Ends - 7:25AM

Observation photos (6)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 80% START 9:00 TO 3:00

    2 ft. - General Observation - 80% START 9:00 TO 3:00

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

    15.4 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUN REBAR UNDER MAG COATSPORATIC

    71.7 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUN REBAR UNDER MAG COATSPORATIC

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    115.1 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    284.1 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (15)

DistanceCodeObservation
2SAMSEVERE AGG
546MGOMAG COAT 80% FINISH
0MWL
2MGO80% START 9:00 TO 3:00
546.7AMH7:25AM
546MGOMH CONN 3:00 ACTIVE
15.4SRVCIRCUM REBAR UNDER MAG COAT
0MWM
284.1SRVCIRCUM REBAR
71.7SRVCIRCUN REBAR UNDER MAG COATSPORATIC
546SAMSEVERE AGG
174.1SRV
546MGOMH CONN OPEN 9:00
115.1SRVCIRCUM REBAR
0AMH6:55AM

Properties (5)

custom_field_two
CIRCUM REBAR VISIBLE
customer
LACSD
datetime
2017-08-05T02:06:25-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false