Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2016, 12:36 AM
  • 14 0247A_14 0838 _02022017_022052.mp4

Date
12/19/2016
W/O
613594
Weather
Heavy Rain
Operator/Surveyor
JUAN B
Sewer ID
Z00569
PipeID
P20828
Time
4:36 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4228
Sewer Name
14 AVENUE "H" TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_613594_TV14037_JAN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
14 0247A
Downstream MH
14 0838
Dir. of Survey
Downstream
Length Surveyed
278.1 ft.
Total Length
278.1 ft.
Structural Index
3
Structural Quick
3J2E
Structural Rating
226
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
334
Pipe schematic from manhole 14 0247A to 14 0838
MH: 14 0247AMH: 14 0838downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 0247A6.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start6.8 ft. MGO - General Observation - MAG COATING116.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start199 ft. MGO - General Observation - RUN LIST STATES MH AT 185'278.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0838278.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish278.1 ft. MGO - General Observation - ACTIVE CONNECTION AT 9 O CLOCK278.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish278.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    6.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    116.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
6.8DAGS
278.1AMH14 0838
6.8SAV
0MWL
278.1SAV
0MWM
116.4SSS
278.1MGOACTIVE CONNECTION AT 9 O CLOCK
199MGORUN LIST STATES MH AT 185'
6.8MGOMAG COATING
0AMH14 0247A
278.1DAGS
278.1SSS

Properties (6)

additional_info
SC306730
custom_field_two
3
customer
LACSD
datetime
2016-12-19T16:36:29-08:00
documentation
PROPIPE
is_lateral_inspection
false