Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2017, 08:18 PM
  • 21 1281_21 1280 _26012017_121927.mpg

Date
01/26/2017
W/O
613587
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00763
PipeID
P24597
Time
12:18 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4135
Sewer Name
21 DISTRICT #21 OUTFALL TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
28
Purpose
Routine Assessment
Project
WO_613587_TV21075_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
21 1281
Downstream MH
21 1280
Dir. of Survey
Downstream
Length Surveyed
552.4 ft.
Total Length
552.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3U00
O&M Rating
324
Overall Index
3
Overall Quick
Overall Rating
324
Pipe schematic from manhole 21 1281 to 21 1280
MH: 21 1281MH: 21 1280downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 128112.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start302.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"370.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"552.4 ft. AMH - Downstream Manhole, Survey Ends - 21 1280552.4 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    12.9 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
552.4AMH21 1280
370.4TF
0MWM
552.4DSZ
0MWL
12.9DSZ
302.8TF
0AMH21 1281

Properties (7)

additional_info
SC306491
custom_field_two
4
customer
LACSD
datetime
2017-01-26T12:18:46-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37161