Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2017, 10:35 AM
  • 18 0627_18 0625 _01052017_030525.mpg

Date
01/05/2017
W/O
613547
Weather
Light Rain
Operator/Surveyor
R.VARGAS
Sewer ID
Z00692
PipeID
P14478
Time
2:35 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4063
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_613547_TV18085_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0627
Downstream MH
18 0625
Dir. of Survey
Downstream
Length Surveyed
672.2 ft.
Total Length
672.2 ft.
Structural Index
5
Structural Quick
5600
Structural Rating
30
O&M Index
2
O&M Quick
2Z11
O&M Rating
267
Overall Index
2
Overall Quick
Overall Rating
297
Pipe schematic from manhole 18 0627 to 18 0625
MH: 18 0627MH: 18 0625downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 06270 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3 ft. MGO - General Observation - MAGNESIUM H.O. START339.4 ft. MGP - General Photograph475.5 ft. LL - Alignment Left, 10 %637.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start637.6 ft. MMC - Material Change, Reinforced concrete pipe668 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish668.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish668.4 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH672.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE672.2 ft. MGO - General Observation - CCTV FOOTAGE DIFFERENT FROM SPREAD SHEET672.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0625

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph

    339.4 ft. - General Photograph

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    637.6 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
0AMH18 0627
0MWM
339.4MGP
672.2MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
637.6SRV
475.5LL
0MWL
2.1DAGS
637.6MMC
668SRV
672.2MGOCCTV FOOTAGE DIFFERENT FROM SPREAD SHEET
668.4DAGS
672.2AMH18 0625
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
668.4MGOMAGNEZIUM H.O. FINISH
3MGOMAGNESIUM H.O. START

Properties (6)

additional_info
SC318604
custom_field_two
2
customer
LACSD
datetime
2017-01-05T02:35:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false