Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 3, 2017, 12:18 PM
  • 18 0648_18 0647 _01032017_042926.mp4

Date
01/03/2017
W/O
613547
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00692
PipeID
P14498
Time
4:18 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4061
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
WO_613547_TV18085_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0648
Downstream MH
18 0647
Dir. of Survey
Downstream
Length Surveyed
290.1 ft.
Total Length
290.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J12
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
116
Pipe schematic from manhole 18 0648 to 18 0647
MH: 18 0648MH: 18 0647downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06480 ft. VC - Vermin Cockroach2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start286.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290.1 ft. VC - Vermin Cockroach290.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0647

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
290.1VC
286.4DAGS
0MWL
290.1AMH18 0647
0MWM
2.1DAGS
0AMH18 0648
0VC

Properties (6)

additional_info
SC318602
custom_field_two
4
customer
LACSD
datetime
2017-01-03T04:18:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false