Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2016, 11:13 AM
Date
04/28/2016
W/O
563407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00326
PipeID
P08355
Time
4:13 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3333
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV CONNECTION
City
LAWNDALE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
V
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
A 0574
Downstream MH
A 0573
Dir. of Survey
Downstream
Length Surveyed
54.8 ft.
Total Length
54.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
513B
O&M Rating
47
Overall Index
3
Overall Quick
Overall Rating
47
Pipe schematic from manhole A 0574 to A 0573
MH: A 0574MH: A 0573downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05740 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start40.3 ft. OBM - Obstacles Pipe Material, 15 %of cross sectional area, from 04 to 08 o'clock, Start54.8 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish54.8 ft. OBM - Obstacles Pipe Material, 15 %of cross sectional area, from 04 to 08 o'clock, Finish54.8 ft. OBM - Obstacles Pipe Material, 40 %of cross sectional area, from 04 to 10 o'clock54.8 ft. MSA - Survey Abandoned - DUE TO PIPE MATERIAL.

Observations (10)

DistanceCodeObservation
0MWM
54.8DAE
54.8OBM
0AMHA 0574
40.3OBM
0MWL
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2DAE
54.8OBM
54.8MSADUE TO PIPE MATERIAL.

Properties (6)

additional_info
SC305607
custom_field_two
5
customer
LACSD
datetime
2016-04-28T04:13:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false