Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 06:43 AM
Date
04/05/2016
W/O
563407
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00327
PipeID
P08349
Time
11:43 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3245
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE, CA 90260
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
A 0568
Downstream MH
A 0567
Dir. of Survey
Downstream
Length Surveyed
270.9 ft.
Total Length
270.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
4221
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole A 0568 to A 0567
MH: A 0568MH: A 0567downstream0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - A 05680 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area3.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start21.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start30.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish52 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"95.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"125.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"212.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.9 ft. RMB - Roots Medium Barrell, at 10 o'clock, 35 %, within 8 inches of joint: NO215.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.5 ft. RMB - Roots Medium Barrell, from 02 to 04 o'clock, 30 %, within 8 inches of joint: NO263.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish270.9 ft. AMH - Downstream Manhole, Survey Ends - A 0567

Observations (22)

DistanceCodeObservation
165.8TFC
263.5RMB
95.2TFA
3.4DAGS
168.1TFA
0MGOLATERAL AT MH 3 OCLOCK
125.5TFA
212.9TFA
212.9RMB
0AMHA 0568
268.4DAGS
52TFA
215.9TFA
0MGOLATERAL AT MH 9 OCLOCK
21.7SSS
30.7SSS
0MWM
263.5TF
131.8TFC
259.1TFC
270.9AMHA 0567
0MWL

Properties (6)

additional_info
SC305337
custom_field_two
4
customer
LACSD
datetime
2016-04-05T23:43:51-07:00
documentation
PRO-PIPE
is_lateral_inspection
false