Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2016, 07:22 AM
Date
04/19/2016
W/O
563407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00327
PipeID
P08336
Time
12:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3320
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
A 0555A
Downstream MH
A 0555
Dir. of Survey
Downstream
Length Surveyed
327.2 ft.
Total Length
327.2 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
412L
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole A 0555A to A 0555
MH: A 0555AMH: A 0555downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 0555A0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start33.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"42.3 ft. CS - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES44.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"99 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"157.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES204.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"244.6 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES246.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"303.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish327.2 ft. AMH - Downstream Manhole, Survey Ends - A 0555

Observations (22)

DistanceCodeObservation
327.2AMHA 0555
189.8CL
44.2TFA
244.6CS
246.9TF
276.9TFA
33.4TF
2DAGS
204.1TFA
42.3CS
0MWL
75.8TFA
261.9TFA
99TFA
0AMHA 0555A
126.3TF
157.3TF
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
303.7TF
325.4DAGS
184.8TF
0MWM

Properties (6)

additional_info
SC305447
custom_field_two
4
customer
LACSD
datetime
2016-04-19T00:22:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false