Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2016, 08:56 AM
Date
04/19/2016
W/O
563407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00327
PipeID
P08332
Time
1:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3320
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
A 0552
Downstream MH
A 0551
Dir. of Survey
Downstream
Length Surveyed
353.6 ft.
Total Length
353.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312M
O&M Rating
145
Overall Index
2
Overall Quick
Overall Rating
145
Pipe schematic from manhole A 0552 to A 0551
MH: A 0552MH: A 0551downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05520 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start31 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"91.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"123 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"206 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES206 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS256.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"271.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"338.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"351.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353.6 ft. AMH - Downstream Manhole, Survey Ends - A 0551

Observations (15)

DistanceCodeObservation
206RML
123TFA
206TFDROOTS
0MWL
338.8TFA
0AMHA 0552
2DAGS
256.1TFA
351.4DAGS
170.6TFA
271.3TFA
0MWM
31TFA
353.6AMHA 0551
91.4TFA

Properties (6)

additional_info
SC305447
custom_field_two
4
customer
LACSD
datetime
2016-04-19T01:56:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false