Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2016, 08:21 AM
Date
04/19/2016
W/O
563407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00327
PipeID
P08334
Time
1:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3320
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
A 0554
Downstream MH
A 0553
Dir. of Survey
Downstream
Length Surveyed
350.3 ft.
Total Length
350.3 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
2V00
O&M Rating
228
Overall Index
2
Overall Quick
Overall Rating
237
Pipe schematic from manhole A 0554 to A 0553
MH: A 0554MH: A 0553downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05542 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start39.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"89.8 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS99.3 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES121.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish130.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES156.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 65"168.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start199.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish280 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"313 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES322.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start348.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish348.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish350.3 ft. AMH - Downstream Manhole, Survey Ends - A 0553

Observations (24)

DistanceCodeObservation
348.1DAGS
329.7DAE
348.1DAE
2DAGS
252.3DAE
78.7TFA
211.1TFA
89.8TFDROOTS
130.9CM
156.9TFA
350.3AMHA 0553
99.3CM
128.5DAE
13DAE
199.6TFA
39.6TFA
280TFA
313CM
0MWM
0MWL
168.3DAE
322.5TFA
121.9TFA
0AMHA 0554

Properties (6)

additional_info
SC305447
custom_field_two
4
customer
LACSD
datetime
2016-04-19T01:21:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false