Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 07:15 AM
  • 15 0614_15 0613A_06042016_001647.mp4

Date
04/06/2016
W/O
563459
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P24099
Time
12:15 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3309
Sewer Name
15 DOUBLE AVENUE TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_563459_TV15205_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
15 0614
Downstream MH
15 0613A
Dir. of Survey
Downstream
Length Surveyed
233.6 ft.
Total Length
233.6 ft.
Structural Index
3
Structural Quick
4G3I
Structural Rating
311
O&M Index
2
O&M Quick
2H00
O&M Rating
94
Overall Index
3
Overall Quick
Overall Rating
405
Pipe schematic from manhole 15 0614 to 15 0613A
MH: 15 0614MH: 15 0613Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06142 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES8.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start16.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish30 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start49.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS76.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 2"231.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish231.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish231.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish233.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0613A233.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.233.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK233.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    4 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    8.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    30 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    49.4 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

Observations (24)

DistanceCodeObservation
76.7TF
101.3TF
16.2TFC
231.7FM
233.6AMH15 0613A
149.3TF
2SAP
231.7SAP
24.4FL
0MWL
4FM
233.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
49.4TFDROOTS
224.7TF
8.9FL
233.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
0AMH15 0614
2DAGS
231.7DAGS
233.6MGOCOCKROACHES IN MANHOLE
128.1TFA
30FM
227.3TF

Properties (6)

additional_info
SC305435
custom_field_two
2
customer
LACSD
datetime
2016-04-06T00:15:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false