Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2017, 07:32 AM
Date
04/14/2017
W/O
630215
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00598
PipeID
P20532
Time
12:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4466
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_630215_TV15018_APR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0343
Downstream MH
15 0342A
Dir. of Survey
Downstream
Length Surveyed
173.7 ft.
Total Length
173.7 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
102
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
102
Pipe schematic from manhole 15 0343 to 15 0342A
MH: 15 0343MH: 15 0342Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 03433.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish173.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK173.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0342A

Observations (11)

DistanceCodeObservation
0MWM
3.3SAV
173.7MGOCONNECTION AT MH 9 O'CLOCK
173.6SAV
0MWL
173.7AMH15 0342A
129.2TFC
21.8TF
0MGOCONNECTION AT MH 9 O'CLOCK
0AMH15 0343
28.4TFC

Properties (6)

additional_info
SC345175
custom_field_two
3
customer
LACSD
datetime
2017-04-14T00:32:43-07:00
documentation
PROPIPE
is_lateral_inspection
false