Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 29, 2016, 08:46 AM
  • 18 0750_18 0749_20160429_020505.mpg

Date
04/29/2016
W/O
568699
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14603
Time
1:46 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3357
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_568699_TV18103_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
18 0750
Downstream MH
18 0749
Dir. of Survey
Downstream
Length Surveyed
431.4 ft.
Total Length
431.4 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0750 to 18 0749
MH: 18 0750MH: 18 0749downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07500 ft. MWM - Water Mark, 25 %of cross sectional area7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start428.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish428.3 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish431.4 ft. MGO - General Observation - CONNECTION AT MH 8 OCLOCK431.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0749431.4 ft. MGO - General Observation - CONNECTION AT MH 1 OCLOCK

Observation photos (3)

  • Water Mark, 25 %of cross sectional area

    0 ft. - Water Mark, 25 %of cross sectional area

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
7SAP
431.4MGOCONNECTION AT MH 8 OCLOCK
428.3SAP
431.4AMH18 0749
428.3SRV
7SRV
431.4MGOCONNECTION AT MH 1 OCLOCK
0MWL
0AMH18 0750
0MWM

Properties (5)

additional_info
SC300353
custom_field_two
2
customer
LACSD
datetime
2016-04-29T01:46:47-07:00
is_lateral_inspection
false