Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2017, 10:34 AM
  • 14 0569_14 0568 _30052017_033531.mp4

Date
05/30/2017
W/O
635594
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00581
PipeID
P18665
Time
3:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4564
Sewer Name
14 TRUNK "E"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_635594_TV14049_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0569
Downstream MH
14 0568
Dir. of Survey
Downstream
Length Surveyed
38.9 ft.
Total Length
38.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3127
O&M Rating
17
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 14 0569 to 14 0568
MH: 14 0569MH: 14 0568downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 05692 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start38.9 ft. MSA - Survey Abandoned - DUE TO DEBRIS38.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS38.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - DEBRIS

    38.9 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS

Observations (7)

DistanceCodeObservation
2DAGS
38.9MSADUE TO DEBRIS
38.9DSZDEBRIS
0MWM
38.9DAGS
0MWL
0AMH14 0569

Properties (6)

additional_info
SC345240
custom_field_two
5
customer
LACSD
datetime
2017-05-30T03:34:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false