Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2017, 09:31 AM
  • 15 0944_15 0943 _20170526_042036.mp4

Date
05/26/2017
W/O
635526
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00635
PipeID
P12073
Time
2:31 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4532
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_635526_TV15082_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0943
Downstream MH
15 0944
Dir. of Survey
Upstream
Length Surveyed
232.5 ft.
Total Length
232.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Q18
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
192
Pipe schematic from manhole 15 0943 to 15 0944
MH: 15 0943MH: 15 0944upstream0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 15 0944178.1 ft. LR - Alignment Right, 5 %, Finish217.7 ft. LR - Alignment Right, 5 %, Start228.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start228.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start232.5 ft. MWM - Water Mark, 35 %of cross sectional area232.5 ft. MWL - Water Level, 30 %of cross sectional area232.5 ft. AMH - Downstream Manhole, Survey Begins - 15 0943

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Alignment Right, 5 %, Start

    14.8 ft. - Alignment Right, 5 %, Start

Observations (10)

DistanceCodeObservation
14.8LR
4DAE
4DAGS
232.5DAE
232.5DAGS
0MWM
0MWL
54.4LR
0AMH15 0943
232.5AMH15 0944

Properties (7)

additional_info
SC340746
custom_field_two
3
customer
LACSD
datetime
2017-05-26T02:31:02-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30503