Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 17, 2017, 10:48 AM
  • 15 0564_15 0563 _17042017_034948.mp4

Date
04/17/2017
W/O
630147
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00629
PipeID
P12493
Time
3:48 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4468
Sewer Name
15 SANTA ANITA OUTFALL TRUNK
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
WO_630147_TV15085_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0563
Downstream MH
15 0564
Dir. of Survey
Upstream
Length Surveyed
416.6 ft.
Total Length
416.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3123
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0563 to 15 0564
MH: 15 0563MH: 15 0564upstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 15 056464.4 ft. RFJ - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES80.5 ft. RMJ - Roots Medium Joint, from 07 to 09 o'clock, 15 %, within 8 inches of joint: YESR83.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES213.6 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES217.6 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YES234.3 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"334.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.3 ft. RFC - Roots Fine Connection, from 09 to 10 o'clock334.3 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"338.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 02 o'clock, , within 8 inches of joint: YES353.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 03 o'clock, , within 8 inches of joint: NO360.8 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"416.6 ft. MWL - Water Level, 15 %of cross sectional area416.6 ft. MWM - Water Mark, 35 %of cross sectional area416.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK416.6 ft. AMH - Downstream Manhole, Survey Begins - 15 0563

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 03 o'clock,  , within 8 inches of joint: NO

    63.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 03 o'clock, , within 8 inches of joint: NO

  • Deposits Attached Grease, 5 %of cross sectional area, at 02 o'clock,  , within 8 inches of joint: YES

    78.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 02 o'clock, , within 8 inches of joint: YES

  • Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YES

    199 ft. - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

    203 ft. - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock,  , within 8 inches of joint: YES

    332.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES

  • Roots Medium Joint, from 07 to 09 o'clock, 15 %, within 8 inches of joint: YESR

    336.1 ft. - Roots Medium Joint, from 07 to 09 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

    352.2 ft. - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0MWL
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
55.8TB
352.2RFJ
82.3RFC
0AMH15 0563
203RFJ
82.3TB
199RFJ
78.5DAGS
416.6MGOCONNECTION AT MH 9 O'CLOCK
416.6AMH15 0564
63.5DAGS
182.3TB
336.1RMJ
82.4TB
332.9DAGS

Properties (6)

additional_info
SC345177
custom_field_two
4
customer
LACSD
datetime
2017-04-17T03:48:57-07:00
documentation
PROPIPE
is_lateral_inspection
false