Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 2, 2017, 06:49 AM
  • J 0012_J 0010 _20170802_010822.mp4

Date
08/01/2017
W/O
646290
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00060
PipeID
P11596
Time
11:49 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4675
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CIOTY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
WO_646290_TV08100_JUL2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0012
Downstream MH
J 0010
Dir. of Survey
Downstream
Length Surveyed
213.5 ft.
Total Length
213.5 ft.
Structural Index
2
Structural Quick
3G2G
Structural Rating
197
O&M Index
2
O&M Quick
412G
O&M Rating
84
Overall Index
2
Overall Quick
Overall Rating
281
Pipe schematic from manhole J 0012 to J 0010
MH: J 0012MH: J 0010downstream0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00120 ft. MWL - Water Level, 50 %of cross sectional area13.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start13.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start17.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start69.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"151 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish213.5 ft. AMH - Downstream Manhole, Survey Ends - J 0010213.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish213.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish213.5 ft. MGO - General Observation - CONNECTION AT 3 OC

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    13.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    13.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    17.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MWM
173.2TB
13.2DAGS
151TB
69.8TFC
213.5SAV
213.5AMHJ 0010
0AMHJ 0012
112.9TB
13.2SSS
213.5DAGS
103.4TB
0MWL
17.3SAV
213.5SSS
213.5MGOCONNECTION AT 3 OC

Properties (6)

additional_info
SC345613
custom_field_two
3
customer
LACSD
datetime
2017-08-01T23:49:21-07:00
documentation
PROPIPE
is_lateral_inspection
false