Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2017, 08:01 AM
  • 08 0062_08 0061 _28122017_001404.mp4

Date
12/28/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00064
Time
12:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5297
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0061
Downstream MH
08 0062
Dir. of Survey
Upstream
Length Surveyed
298.9 ft.
Total Length
298.9 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole 08 0061 to 08 0062
MH: 08 0061MH: 08 0062upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00623.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish35.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"294.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start298.9 ft. MWL - Water Level, 10 %of cross sectional area298.9 ft. MWM - Water Mark, 20 %of cross sectional area298.9 ft. AMH - Downstream Manhole, Survey Begins - 08 0061298.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
298.9AMH08 0062
0MWM
163.5TFC
0AMH08 0061
27.5TFC
112.3TFA
295.3CM
4.8CM
48.8TF
263.2TF
212TFC
60.8TFC
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (5)

additional_info
SC346771
custom_field_two
3
customer
LACSD
datetime
2017-12-28T00:01:58-08:00
is_lateral_inspection
false