Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2017, 08:57 AM
  • 08 0056_08 0055 _28122017_010927.mp4

Date
12/28/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00058
Time
12:57 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5297
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0056
Downstream MH
08 0055
Dir. of Survey
Downstream
Length Surveyed
267 ft.
Total Length
267 ft.
Structural Index
3
Structural Quick
3K11
Structural Rating
181
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
181
Pipe schematic from manhole 08 0056 to 08 0055
MH: 08 0056MH: 08 0055downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 00560 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.4 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES100.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES146.6 ft. CC - Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES158.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES161 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.1 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES188.2 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES215.8 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES218.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"259.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES262 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"265 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK265 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish267 ft. AMH - Downstream Manhole, Survey Ends - 08 0055267 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (8)

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    98.4 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    128.9 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    146.6 ft. - Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    158.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    183.1 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    188.2 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    215.8 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    259.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
2CM
265MGOSPALLING THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK
161TF
188.2CM
0MWL
100.4TF
259.7CM
265CM
158.2CM
0MGOCONNECTION AT MH 3 O'CLOCK
267AMH08 0055
0AMH08 0056
218.9TF
262TF
215.8CM
128.9CM
40.3TF
98.4CM
146.6CC
267MGOCONNECTION AT MH 3 O'CLOCK
183.1CM
0MWM

Properties (5)

additional_info
SC346771
custom_field_two
3
customer
LACSD
datetime
2017-12-28T00:57:19-08:00
is_lateral_inspection
false