Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2017, 06:45 AM
  • 08 0064_08 0063 _27122017_225748.mp4

Date
12/27/2017
W/O
679275
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00066
Time
10:45 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5297
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_679275_TV08116_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0064
Downstream MH
08 0063
Dir. of Survey
Downstream
Length Surveyed
333.4 ft.
Total Length
333.4 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
264
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
264
Pipe schematic from manhole 08 0064 to 08 0063
MH: 08 0064MH: 08 0063downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00640 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK4.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"94 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"333.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK333.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0063333.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK333.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
333.4MGOCONNECTION AT MH 9 O'CLOCK
4.4FM
94TF
0MWM
0AMH08 0064
0MWL
147.7TFC
333.4AMH08 0063
0MGOCONNECTION AT MH 3 O'CLOCK
42.2TFC
333.4MGOCONNECTION AT MH 3 O'CLOCK
333.4FM
196.6TFC
244.6TF

Properties (5)

additional_info
SC346771
custom_field_two
2
customer
LACSD
datetime
2017-12-27T22:45:42-08:00
is_lateral_inspection
false