Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2016, 09:52 AM
  • B 1080_B 1077 _08242016_031722.mp4

Date
08/24/2016
W/O
585984
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00923
PipeID
P23044
Time
2:52 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3690
Sewer Name
B JOINT OUTFALL B - UNIT 1C REPLACEMENT
City
PICO RIVERA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
WO_585984_TV02129_AUG2016
Sewer Type
Gravity
Material
RGRCP-PTL
Shape
Circular
Height
72 in.
Width
72 in.
Upstream MH
B 1080
Downstream MH
B 1077
Dir. of Survey
Downstream
Length Surveyed
798.9 ft.
Total Length
798.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 1080 to B 1077
MH: B 1080MH: B 1077downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - B 10800 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start798.9 ft. MSA - Survey Abandoned - BOAT STUCK ON WALL OF PIPE IN TURN,798.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
798.9MSABOAT STUCK ON WALL OF PIPE IN TURN,
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
0AMHB 1080
0MWL
798.9DAGS
2DAGS

Properties (6)

additional_info
SC306020
custom_field_two
5
customer
LACSD
datetime
2016-08-24T02:52:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false