Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2016, 11:09 AM
  • F 0150F 0149 District 02_080516_040600.mp4

Date
08/05/2016
W/O
585746
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00037
PipeID
P10182
Time
4:09 AM
Certificate
U507033386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3676
Sewer Name
F JOINT OUTFALL F - UNIT 3B
City
ARTESIA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39A
Purpose
Routine Assessment
Project
WO_585746_TV02209_AUG2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
F 0150
Downstream MH
F 0149
Dir. of Survey
Downstream
Length Surveyed
549.6 ft.
Total Length
549.6 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
5
Pipe schematic from manhole F 0150 to F 0149
MH: F 0150MH: F 0149downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 01500 ft. MGO - General Observation - CONNECTION AT THE MH 6 O'CLOCK ACTIVE0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. MGO - General Observation - MAG.H.C. START 75%2.5 ft. SRCC - Surface Reinforcement Corroded Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start341.7 ft. SRCC - Surface Reinforcement Corroded Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish549.6 ft. MSA - Survey Abandoned - FLOW IS NOT STRONG ENOUGH TO PULL BOAT THROUGH ENTIRE REACH

Observation photos (2)

  • Surface Reinforcement Corroded Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Reinforcement Corroded Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    341.7 ft. - Surface Reinforcement Corroded Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (8)

DistanceCodeObservation
0MWM
0AMHF 0150
0MGOCONNECTION AT THE MH 6 O'CLOCK ACTIVE
549.6MSAFLOW IS NOT STRONG ENOUGH TO PULL BOAT THROUGH ENTIRE REACH
2.5SRCC
341.7SRCC
0MWL
2MGOMAG.H.C. START 75%

Properties (6)

additional_info
SC306006
custom_field_two
5
customer
LACSD
datetime
2016-08-05T04:09:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false